Retro-fitting escape lighting on residential staircases

This article is more than 7 years old

Let me set the scene: a low-rise residential block, probably three or four floors of flats, with a common-parts, concrete, staircase, and fully glazed from top to bottom. When the block was originally built twenty years ago, it was decided that there was no need for escape lighting on the staircase – what with the relatively low height of the building and all that street lighting outside, it could hardly be considered essential.


What’s changed?

Well, Grenfell Tower happened and now those skimped technical specifications are re-cast as human tragedy. It usually takes something like that for us to see the whole story behind the things that we do – or choose not to do.

But let’s be practical about this.

The typical situation is to have a single lighting circuit running the full height of the staircase, probably controlled by an astronomical time-switch. Luminaires will be surface-mounted, CFL, bulkheads and the cabling is (probably) encased in conduits set into the concrete fabric.

The building management has done a new risk assessment following ‘recent events’ and have decided that they need to invest in escape lighting for that staircase. But there is one proviso; the existing wiring needs to be used – there’s no appetite (or budget) for re-wiring.

So what needs to be done?

  • In order for the escape lighting to be properly maintained, the (single source) power supply needs to be permanently live, so that’s the switching facility gone.
  • Because the staircase is very well lit from the windows, the artificial lighting still only needs to function during the hours of darkness, so some switching mechanism is still needed.
  • The new escape lighting provision needs to be configured in such a way that regular testing can be carried out in accordance with standards.

Where does that leave us?

  • Its possible to use mains-borne signalling to switch luminaires, but that doesn’t answer the need for testing the emergency provision. And there are no luminaires on the market that provide that kind of control.
  • Luminaires are available that are fitted with daylight sensors – but, again, this does nothing for emergency testing requirements.
  • It’s not acceptable to test the installation simply by switching off the entire circuit. That would require the staircase to be out-of-bounds while batteries re-charge – and its an escape staircase.

It looks like we’re in the hands of smart controls.

There will be two types of luminaire needed in the new installation; those required only for normal operation  and those also fitted with emergency lighting back-up. Two sets of control signalling will be required; one that switches on normal lights as they are required, while the other will monitor the status of the emergency circuit, LED sources, batteries etc. This requires a wireless solution. Something like a mesh network that provides the connection between the luminaires. Hopefully, the luminaires were originally installed with a line-of-sight layout, to overcome the potential problem of the density of concrete between ground floor and roof blocking the signals.

Not the simple answer that we were looking for?

No, probably not, but that’s because the original scheme was compromised from the start. If someone had shown a bit more imagination during the design phase, there would already be escape lighting on that staircase.

This conversation started with an electrician charged with exactly this task for a building in Yeovil. And in case anyone suggests that it was perfectly reasonable not to include emergency lighting because of the amount of public area lighting available, let me remind them of the day a few years back when the primary substation feeding Yeovil (and Sherborne) went boom – and left us with a very dark night indeed.

Imagination, you see.

Its why we take out insurance – because we choose to imagine the consequences.